beautypg.com

Scanner instruction manual, Snooper mode ( snoopr ) – Precision Digital PD6080 User Manual

Page 35

background image

PD6080/PD6081 Super Snooper Modbus

Scanner Instruction Manual

35

Snooper Mode (Snoopr)

The Snooper mode is used to listen to data being transmitted on the bus. Multiple Snoopers can be
connected to the RS-485 bus and display any process variable. The same process variable can be
displayed in multiple locations. Use the menu below to configure Snooper Mode parameters.

Back To

Forward
to

PVs 1-15 move

to next PV. PV16

moves to t-resp

.

Byte order is

dependent upon

data type.

Function Code

can be either

03, 04, or 65.

Register Number

is selected

by user.

Enter Slave ID

of meter to be

polled by master.

PV can be any

PV from

PV 1-PV 16.

Notes:

1. To minimize the possibility of communication errors and communication break conditions, use a poll

time of 5 seconds or more with slow baud rates (e.g. 4800 bps or less).

2. The response time for scanners set up for Snooper mode must be greater than the Master’s poll time.

This setting corresponds to the time window during which the Snooper listens to the bus for a reply by
the slave device being polled by the master device. As soon as the Snooper detects a new reply on
the bus, the display is updated. If there is no reply within the response time setting, the Snooper goes
into communications break condition.