Model PD6100 Strain Gauge/Load Cell Meter Instruction Manual

75

Noise Filter (filter)

The noise filter is available for unusually noisy signals that cause an
unstable process variable display. The noise filter averages the input
signal over a certain period. The filter level determines the length of time
over which the signal is averaged. The filter level can be set between 2
and 199. The higher the filter level, the longer the averaging time and so
the longer it takes the display to settle to its final value. Setting the filter
level to zero disables the filter function.

Noise Filter Bypass (bypass)

The noise filter bypass changes the behavior of the meter so that small
variations in the signal are filtered out but large abrupt changes in the
input signal are displayed immediately. The bypass value determines
the minimum amount of signal change to be displayed immediately. All
signal changes smaller than the bypass value are filtered or averaged
by the meter. The noise filter bypass may be set between 0.1 and
99.9% of full scale.

Rounding Feature (round)

The rounding feature is used to give the user a steadier display with
fluctuating signals. Rounding is used in addition to the filter function.

Rounding causes the display to round to the nearest value according to
the rounding selected. This setting affects the last two digits, regardless
of decimal point position. See examples below:

Rounding
Selection

Actual
Value

Display
Value

Actual
Value

Display
Value

1 12.022

12.022

12.023

12.023

5 12.022

12.020

12.023

12.025

10 12.024

12.020

12.025

12.030