High alarm with fail-safe operation (set > reset) – Precision Digital PD6100 User Manual

Page 54

background image

Model PD6100 Strain Gauge/Load Cell Meter Instruction Manual

54

High Alarm with Fail-Safe Operation (Set > Reset)

Note: Relay coil is energized in non-alarm condition.

In case of power failure, relay will go to alarm state.

Relay

Input

Automatic (non-latching)

energized

de-energized

off

on

Relay

LED

Automatic or Manual (non-latching)

ACK

pressed

Relay

LED

Manual (latching)

ACK

pressed

Relay

LED

Manual only after passing below Reset (latching with clear)

ACK

pressed

Set

LED