Model PD6100 Strain Gauge/Load Cell Meter Instruction Manual

10

WEIGHT

9.5 oz (269 g)

WARRANTY

3 years parts & labor

Strain Gauge Input

INPUTS

Field selectable: 0-15, 0-30, 0-150, 0-300 mV,
±15, ±25, ±150, ±250 mV, or Modbus PV (Slave)

ACCURACY

±0.03% of calibrated span ±1 count

MINIMUM LOAD
RESISTANCE

28 Ω @ 5 V or 10 V

MAXIMUM
EXCITATION
CURRENT

350 mA @ 5 V or 10 V

TEMPERATURE
DRIFT

0.002% of calibrated span/

C max from 0 to 65C ambient,

0.005% of calibrated span/

C max from -30 to 0C ambient

FUNCTIONS

Linear with multi-point linearization

MULTI-POINT
LINEARIZATION

2 to 32 points for PV or PV1
2 to 8 points for PV2 (Dual-scale feature)

LOW-FLOW
CUTOFF

0-999999 (0 disables cutoff function)

DECIMAL POINT

Up to five decimal places or none:

d.ddddd

, d.dddd, d.ddd, d.dd, d.d,

or

dddddd

CALIBRATION
RANGE

Input
Range

Minimum Span
Input 1 & Input 2

15 mV

0.2 mV

25 mV, 30 mV

0.4 mV

150 mV

2.0 mV

250 mV, 300 mV

4.0 mV

An Error message will appear if the input 1 and input 2
signals are too close together.

INPUT
IMPEDANCE

Strain Gauge Bridge: Greater than 10 MΩ
mV Source: 200 kΩ

Relays

RATING

2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A)
external; rated 3 A @ 30 VDC and 125/250 VAC resistive
load; 1/14 HP (≈ 50 W) @ 125/250 VAC for inductive loads

NOISE
SUPPRESSION

Noise suppression is recommended for each relay contact
switching inductive loads; see page 25 for details.