Model PD6100 Strain Gauge/Load Cell Meter Instruction Manual

64

Application #2: Pump Alternation Using Relays 3 & 4

1. Relays 1 and 2 are set up for low and high alarm indication.
2. Relays 3 and 4 are set up for pump alternation.
Set and Reset Point Programming

Relay

Set Point

Reset Point

Function

1

495

750

Controls low alarm

2

7500

6900

Controls high alarm

3

7000

900

Controls backup pump

4 6000 1000 Controls

main

pump

The following graphics provide a visual representation of a typical pump
alternation application with high and low alarm monitoring.

1. Relay #4 turns the main pump on at 6000 gallons and turns it off at

1000 gallons.

2. With the Pump Alternation feature activated, the next time the level

reaches 6000 gallons, relay #3 transfers and starts the backup
pump.