Interlock relay feature, Figure 21. digital i/o module connections, Figure 22. interlock connections – Precision Digital PD6100 User Manual
Page 28

Model PD6100 Strain Gauge/Load Cell Meter Instruction Manual
28
Figure 21. Digital I/O Module Connections
Interlock Relay Feature
As the name implies, the interlock relay feature reassigns one, or more,
alarm/control relays for use as interlock relay(s). Interlock contact(s) are
wired to digital input(s) and trigger the interlock relay. This feature is
enabled by configuring the relay, and relative digital input(s) (see page
66). In one example, dry interlock contacts are connected in series to
one digital input which will be used to force on (energize) the assigned
interlock power relay when all interlock contacts are closed (safe). The
interlock relay front panel LED flashes when locked out. The interlock
relay would be wired in-series with the load (N/O contact). See below.
Figure 22. Interlock Connections
1
2
3
4
5
6
+5
I1
I2
I3
I4
O1
7
8
O2
O3
9
10
O4
G
DI 1-4
DO 1-4
5 VDC
GND