Setting the relay operation ( relay ) – Precision Digital PD6100 User Manual
Page 49

Model PD6100 Strain Gauge/Load Cell Meter Instruction Manual
49
Setting the Relay Operation (relay)
This menu is used to set up the operation of the relays.
Caution!
During setup, the relays do not follow the
input and they will remain in the state found
prior to entering the Relay menu.
1. Relay
action
a. Automatic reset only (non-latching)
b. Automatic + manual reset at any time (non-latching)
c. Latching (manual reset only)
d. Latching with Clear (manual reset only after alarm
condition has cleared)
e. Pump alternation control (automatic reset only)
f.
Sampling (the relay is activated for a user-specified time)
g. Off (relay state controlled by Interlock feature)
2. Set
point
3. Reset
point
4. Fail-safe
operation
a. On
(enabled)
b. Off
(disabled)
5. Time
delay
a. On delay (0-999.9 seconds)
b. Off delay (0-999.9 seconds)
!