beautypg.com

B-5 battery bank sizing worksheet – Magnum Energy MS-PE Series User Manual

Page 56

background image

©

2013 Magnum Energy, Inc.

Page 49

Appendix B – Battery Information

B-5 Battery Bank Sizing Worksheet

Complete the steps below to determine the battery bank size required to power your AC loads:
1. Determine the daily power needed for each load.

a) List all AC loads required to run; and
b) List the Watt-Hours (Wh) for each load (see Table C-1 for common loads/wattage); and
c) Multiply by how many hours per day (or a fraction of an hour) each load will be used; and
d) Multiply by how many days per week you will use the listed loads; and then
e) Divide by seven = Average Daily Watt-Hours Per Load.

Average Daily Watt-Hours Per Load

AC load

Watt-Hours

(x) hours per day

(x) days per week (

÷

7) = daily Wh/load

4. Determine how deeply you want to discharge your batteries.

• Divide

the

Storage Amp-Hours by 0.2 or 0.5 to get the Total Amp-Hours:

a) 0.2 = Discharges the batteries by 20% (80% remaining), this is considered the

optimal level for long battery life; or

b) 0.5 = Discharges the batteries by 50% (50% remaining), this is considered

a realistic trade-off between battery cost and battery life.

2. Determine the total power needed each day for all the loads.

• Add

the

Average Daily Watt-Hours Per Load together = Total Daily Watt-

Hours.

Total Daily Watt-Hours

Total Amp-Hours

3. Determine the battery Amp-Hour capacity needed to run

all the loads before recharging.

• Divide

the

Total Daily Watt-Hours by the nominal battery voltage of

the inverter (i.e., 12, 24 volts); and

• Multiply this by how many days the loads will need to run without

having power to recharge the batteries (typically 3 to 5 days of

storage) = Storage Amp-Hours.

x ___ =

(days of storage)

÷

___ =

(inverter battery voltage)

Temperature

27C/80F

21C/70F

15C/60F

10C/50F

4C/40F

-1C/30F

-7C/20F

Multiplier

1.00

1.04 1.11

1.19

1.30

1.40 1.59

Additional compensation:

Low battery temperature: If the batteries are installed in a location that will be exposed to low temperatures,

the available output will be less. In these instances, you will need to determine the lowest temperature the

battery bank will experience and multiply the Total Amp-Hours by the Multiplier below.

Inverter effi ciency: When the inverter is used in a back-up power application the inverter effi ciency will not

be a large concern. However, if the inverter is the primary AC source for the calculated load, the Total Amp-

Hours should be multiplied by 1.2 to factor in an average 80% inverter effi ciency.

This manual is related to the following products: