2.6.1

Sizing the Grounding Electrode Conductors

AC Side – The size of the AC grounding electrode conductor (GEC-AC) depends on the size of

the largest ungrounded conductor feeding the AC load center. One 8.4 mm

2

(#8 AWG) copper

conductor will serve as an AC grounding electrode conductor (GEC-AC) for AC power conductors

smaller than and including 33.6 mm

2

(#2 AWG) copper. See

Table 2-3 for additional values.

Table 2-3, AC Grounding Electrode Conductor Sizing

Size of Largest

Ungrounded Conductor

Minimum Size of

Grounding Electrode Conductor

33.6 mm

2

(#2 AWG) or smaller

8.4 mm

2

(#8 AWG)

42.4 to 53.5 mm

2

(#1 to #1/0 AWG)

13.3 mm

2

(#6 AWG)

67.4 or 85.0 mm

2

(#2/0 or #3/0 AWG)

21.1 mm

2

(#4 AWG)

85.0 mm

2

(Over #3/0 AWG) thru 350 kcmil

33.6 mm

2

(#2 AWG)

DC Side – To size the DC grounding electrode conductor (GEC-DC), you must fi rst determine

which one of the following three methods will be used to connect the DC and AC grounding points

in the inverter’s two electrical systems to the common earth ground:
Method 1 (Figure 2-11): This method uses a separate grounding electrode for the DC system

and the AC system. In this method—since there are multiple connections to the DC grounding

electrode (GE-DC)—the size of the DC grounding electrode conductor (GEC-DC) cannot be

smaller than the largest conductor in the DC system (usually the battery-to-inverter cable).
The DC grounding electrode (GE-DC) must be bonded to the AC grounding electrode (GE-AC)

to establish a grounding electrode system; this bonding conductor (BC) cannot be smaller than

the largest grounding electrode conductor (GEC), either AC or DC.

Figure

2-11, Multiple Connections to DC Ground Rod (Method 1)

AC

DC Service

Panel

AC Service

Panel

DC Electrical System

AC Electrical System

Neutral

Positive

Negative

DC

Grounding

System

Negative

SBJ

GC

GEC-AC

EGC - AC

AC Ground

DC Ground

SBJ

EGC - DC

GC

Neutral

Hot

GEC-DC

GE

GE

GBB

GBB

Grounding Electrode

(DC side dedicated)

Grounding Electrode

(AC side dedicated)

MS-PE Series Inverter/Charger

BC