Method 3 (Figure 2-13): The AC grounding electrode conductor (GEC-AC) is bonded to the

DC ground point and the DC grounding electrode conductor (GEC-DC) is the only connection

to the grounding electrode (GE), which must be a rod, pipe, or plate electrode.
In this method, since there is only one connection to the ground rod, the DC grounding

electrode conductor (GEC-DC) is not required to be larger than 13.3 mm

2

(#6 AWG) copper.

The reasoning for allowing this smaller grounding electrode conductor is that it is only required

to stabilize the system voltage with respect to earth, and the other properly sized conductors

in each electrical system will safely carry any fault currents if they occur.

Method 2 (Figure 2-12): When the AC and DC service panels are near each other, the AC

grounding electrode conductor (GEC-AC) and the DC grounding electrode conductor (GEC-DC)

can be connected to a single grounding electrode (GE). In this method—since there are multiple

connections to the DC grounding electrode (GE-DC)—the size of the DC grounding electrode

conductor (GEC-DC) cannot be smaller than the largest conductor in the DC system (usually

the battery-to-inverter cable).

AC

DC Service

Panel

AC Service

Panel

DC Electrical System

AC Electrical System

Neutral

Positive

Negative

DC

Grounding

System

Negative

SBJ

GC

GE

GEC-AC

EGC - AC

AC Ground

DC Ground

SBJ

EGC - DC

GC

Neutral

Hot

GEC-DC

GBB

GBB

Grounding Electrode

(AC and DC sides shared)

MS-PE Series Inverter/Charger

Figure

2-12, Multiple Connections to DC Ground Rod (Method 2)

Figure 2-13, Single Connection to DC Ground Rod (Method 3)

AC

DC Service

Panel

AC Service

Panel

DC Electrical System

AC Electrical System

Neutral

Positive

Negative

DC

Grounding

System

Negative

SBJ

GC

GEC-AC

EGC - AC

AC Ground

DC Ground

SBJ

EGC - DC

GC

Neutral

Hot

GEC-DC

GE

GBB

GBB

Grounding Electrode

(DC side dedicated)

MS-PE Series Inverter/Charger

This manual is related to the following products: