beautypg.com

Magnum Energy MS-PE Series User Manual

Page 33

background image

Page 26

©

2013 Magnum Energy, Inc.

Installation

2.6.4

Grounding on Boats

When installing the MS-PE Series inverter/charger on a boat, there are several considerations that

must be followed when grounding to ensure a safe installation, prevent galvanic corrosion, and

adhere to local codes and industry standards.
Ensure a Safe Ground Connection
When AC on the boat is being supplied by shorepower, the onboard neutral should be connected

to safety ground on the dock. Consequently, neutral and safety ground should not be connected

anywhere on the boat when shorepower is present. When AC on the boat is being supplied by

the MS-PE Series inverter, the inverter’s output neutral is connected to safety ground through an

internal relay using its neutral-to-ground connection (see Figure 2-16).
The DC ground terminal on the MS-PE Series must also be connected to the boat’s safety ground

bus. This ensures that both the inverter’s AC and DC ground terminals are connected to the boat’s

safety ground bus as a safety measure to provide protection against faults, and to provide a path

for AC fault currents while the boat is connected to shorepower.
Preventing the Risk of Corrosion
The inverter’s AC and DC ground terminals must be connected to the boat’s safety ground to

provide an important safety feature. However, this ground connection introduces the risk of galvanic

corrosion and/or electrolysis of the boat’s underwater metallic hardware.
Two possible solutions are typically used to maintain the correct onboard grounding requirements

while greatly reducing (if not eliminating) the risk of galvanic corrosion. These solutions would be

either using a galvanic isolator or an onboard isolation transformer.
Galvanic isolators allow high AC voltage faults to pass, but block low voltage corrosion/electrolysis

currents from conducting.
Marine isolation transformers enable the shorepower to be connected to one side of the transformer

while the boat’s AC wiring system is connected to the other side. Since transformers do not allow

DC currents to pass, the problem with galvanic corrosion is eliminated.
Recommended Inverter/Charger Grounding Requirements
• DC Grounding Connections:

1. The DC grounding conductor (equipment ground) shall be:

a) Connected from the metallic case or chassis of the inverter/charger to the engine negative

terminal or its bus;
b) and, an ampacity equal to that of the DC positive conductor (under certain conditions

there may be an exception to allow this conductor to be one size smaller—refer to local

standards).

2. The inverter/charger’s negative battery terminal and DC grounded conductor (negative

cable) shall not be connected to the inverter case or chassis at the inverter/charger itself.

• AC Grounding Connections:

1. The AC grounding conductor (green w/yellow stripe) shall be connected to the inverter/

charger in a manner so that the AC ground connection will not be disconnected in servicing.

This conductor is in addition to and independent of the DC grounding conductor.

2. The neutral for AC power sources shall be grounded only at the following points:

a) The shorepower neutral is grounded only through the shorepower cable and not grounded

on board the boat.
b) The inverter neutral shall be grounded at the inverter, and the output neutral shall be

disconnected from ground when the inverter is operating in the charger/pass-through mode.
c) On systems using an isolation transformer or a polarization transformer, the inverter

neutral (and the transformer secondary neutral) may be grounded at the AC main grounding

bus instead of at the inverter.

This manual is related to the following products: