Installation

2.7 Inverter

Notifi cation Requirements

When an inverter is installed in a building, facility or structure, standard safety practices require a

label or plaque be present. This label/plaque is required to be readily visible and provide information

that informs personnel to the location of all electrical system disconnects. This is to ensure all

power to a building is quickly located and shut down in an emergency. There are also specifi c

requirements for this label/plaque depending on the inverter application, they are as follows:
Facilities with Standalone Systems – Any building, facility, or structure with a photovoltaic

power system that is not connected to a utility service source and is a standalone system, must

have a permanent plaque or directory installed on the exterior of the building or structure at

a readily visible location acceptable to the Authority Having Jurisdiction (AHJ). The plaque or

directory must provide the location of system disconnecting means, and include information

regarding whether the structure contains a standalone electrical power system.

Facilities with Utility Services and PV Systems Buildings, facilities, or structures with

both utility service and a photovoltaic system must have a permanent plaque or directory

providing the location of the service disconnecting means and the photovoltaic system

disconnecting means, if they are not located at the same location.

2.7.1

Inverter Warning Label

A warning label as shown in Figure 2-18 is provided to inform all personnel that an inverter is

installed in your electrical system. Affi x this label in a clearly visible location at the electrical panel

that is being powered by the inverter. This is because it might be falsely assumed that the panel is

no longer “hot” after the AC power has been shut off, when power may actually still be available

due to the inverter automatically powering the panel.

This electrical system is equipped with an Automatic
Generator Starting (AGS) device and/or an inverter.
Disconnect all AC and DC power to the AGS and/or
inverter before performing any service to the electrical
system. Failure to do so can result in shock causing
serious injury or death.

PN: 62-0002 Rev A

This electrical system is equipped with an Automatic
Generator Starting (AGS) device and/or an inverter.
Disconnect all AC and DC power to the AGS and/or inverter
before performing any service to the electrical system.
Failure to do so can result in shock causing serious injury
or

death.

PN: 62-0002 Rev A

Figure 2-18, Warning Label

2.8 Final

Inspection

1. Verify all cables/conduit runs are secured with wire ties or other non-conductive fasteners to

prevent chafi ng or damage from movement and vibration.

2. Verify strain reliefs or grommets are in place to prevent damage to the wiring or conduit where

it passes through walls, bulkheads, or other openings.

3. Verify all AC connections are correct and torqued to a maximum of 1.8 N-m (16 in lbf).
4. Replace the covers on the main electrical/distribution panel.
5. Replace the chassis access cover.
6. Verify the inverter’s front panel switch is in the OFF position.

Info: If required by code, have the installation inspected by an electrical inspector.