3.0 Operation

The MS-PE Series inverter has two normal operating routines; Inverter mode, which powers your

loads using the batteries, and Standby mode, which transfers the incoming AC power (e.g., utility

power or a generator) to power your loads and to recharge the batteries. This inverter also includes

an extensive protection circuitry to shut down the inverter under certain fault conditions.

3.1 Inverter

Mode

When the MS-PE Series is fi rst powered up, it defaults to the OFF mode.

The momentary ON/OFF

power switch (

see Figure 1-1, Item 1) m

ust be lightly pressed to turn the inverter on. Subsequently,

pressing this switch alternately turns the inverter off and on.

Inverter OFF

When the inverter is off,

no power is used from the batteries to power the AC

loads, and

the status

LED will be off. If AC power from an external source (utility grid or generator)

is connected and qualifi ed on the inverter’s AC input, this AC input power will pass through the

inverter to power the AC loads. However, if this AC power is lost, the AC loads will no longer be

powered because the inverter is off.
When the inverter is turned on, it operates either by “searching” or “inverting”, depending on the

connected AC loads.
Searching – When the inverter is fi rst turned on, the automatic Search feature is enabled. This

feature is provided to conserve battery power when AC power is not required. In this mode, the

inverter pulses the AC output looking for an AC load (e.g., electrical appliance). Whenever an AC load

(greater than 5 watts) is turned on, the inverter recognizes the need for power and automatically

starts inverting. When there is no load (or less than 5 watts) detected, the inverter automatically

goes back into Search mode to minimize energy consumption from the battery bank. When the

inverter is searching, the inverter’s green LED fl ashes (fast).

Info: The factory default value for the Search feature is 5 watts, it can be turned off

or adjusted from 5 to 50 watts using a remote display (ME-RC, ME-ARC, or ME-RTR).

Inverting

When a load greater than 5 watts is connected to the inverter output, the MS-PE

Series inverts the DC power from the battery and supplies 230 VAC power to your sub-panel. The

inverter’s green LED fl ashes once every 2 seconds (medium fl ash) to indicate it is inverting. The

amount of time the inverter can be inverting and

providing power is directly related to the amount

of AC loads that are connected, and the capacity of the battery bank. Refer to Figure 3-1 to see

the fl ow of power from the DC input to the AC output while in the Inverter mode.

230

VAC

INV

OUT

AC Hot

Transfer Relay

AC NEUT IN

AC HOT IN

CB1 (30A)

AC GROUND

Power Transformer

FET Bridge

AC

DC

DC

IN

AC NEUT OUT

AC HOT OUT

DC POSITIVE

DC NEGATIVE

Figure 3-1, Power Flow - Inverter Mode