Installation

2.6.6

Disabling the Neutral-to-Ground Connection

All MS-PE Series inverter/chargers have the automatic neutral-to-ground switching feature. In

some installations/jurisdictions, this feature must be disabled. If you are not sure whether you must

disable this feature, check your local code requirements. The following steps will guide you in disabling

the neutral-to-ground switching feature in the MS-PE Series inverter/charger.

Info: The ground connection from the inverter’s AC and DC ground terminals should

still be connected to the system ground even if ground switching has been disabled.

WARNING: Fire and Shock Hazard – disconnect all AC and DC sources before working

in the AC wiring compartment.

1. Locate and remove the AC Access Cover plate

(see Figure 1-3, Item 15) on the side of the

MS-PE Series inverter.

2. Look inside and locate the green wire with

the insulated connector at the top of the AC

wiring compartment; see Figure 2-16. This

insulated connector connects the neutral and

ground inside the inverter.

3. Pull the two ends of the insulated connector

apart to separate the green wire. This will

prevent the neutral and ground from con-

necting inside this inverter.

4. Move the two disconnected ends away from

each other and push back out of the way. You

must ensure that the two connector ends will

not have any contact with any other wires

within the AC compartment. You may want

to use electrical tape to insulate the ends

and secure them out of the way.

Figure 2-16, Disconnecting the

Neutral-to-Ground Connection

2.6.7

Connecting a Large Ground Wire

If your installation requires a larger ground wire than what has been provided, follow the steps

below to connect the larger wire.
1. Locate the DC Equipment Ground Terminal

(see Figure 1-2, Item 7).

2. Locate and remove the AC Access Cover plate

(see Figure 1-3, Item 15) on the side of the

MS-PE inverter.

3. Within the AC wiring area, locate the hex nut

on the back side of the DC ground termi-

nal. After locating the hex nut, use a 7/16”

wrench/nut driver to remove the hex nut,

bolt, lock washer, and DC ground terminal,

and then remove them from the chassis.

4. Reverse the removed bolt, and place it back

in the chassis hole to attach a correctly sized

ground cable to the MS-PE Series chassis, as

shown in Figure 2-17.

5. Place the washer and nut on the bolt, over

the ground cable, and securely tighten the

nut [from 4 to 5 ft lbf (5.4 to 6.8 N-m)].

Replace AC Access Cover plate and secure.

Figure 2-17, Large Ground Wire

Connected to MS-PE Series

DC Ground

Terminal bolt/nut,

reversed and

tightened

Neutral-to-

Ground

Connection

(green wire)