beautypg.com

4 transfer time, 5 battery temperature sensor operation, Operation 3.4 transfer time – Magnum Energy MS-PE Series User Manual

Page 41: Temperature compensation using bts

background image

Page 34

©

2013 Magnum Energy, Inc.

Operation

3.4 Transfer

Time

While in Standby mode, the AC input is continually monitored. Whenever AC power falls below

the VAC dropout voltage (150 VAC, default setting), the inverter automatically transfers back to

Inverter mode with minimum interruption to your appliances—as long as the inverter is turned

on. The transfer from Standby mode to Inverter mode occurs in approximately 16 milliseconds.

While the MS-PE Series is not designed as a computer UPS system, this transfer time is usually

fast enough to hold them up. However, the VAC dropout setting has an effect on the ability of the

loads to transfer without resetting. The lower this setting, the longer the effective transfer will be

and therefore, the higher the probability for the output loads to reset. This occurs because the

incoming AC voltage is allowed to fall to a level that is so low that when the transfer does occur,

the voltage on the inverters output has already fallen to a level low enough to reset the loads.
The disadvantage of a higher VAC dropout setting is that smaller generators (or large generators

with an unstable output) may nuisance transfer. This commonly happens when powering loads that

are larger than the generator can handle—causing the generator’s output voltage to constantly

fall below the inverter’s input VAC dropout threshold.

Info: When switching from Inverter mode to Standby mode, the inverter waits

approximately 15 seconds to ensure the AC source is stable before transferring.

3.5 Battery Temperature Sensor Operation

The plug-in Battery Temperature Sensor (BTS) is used to determine the battery’s temperature.

This information allows the multi-stage battery charger to automatically adjust the battery charge

voltages for optimum charging performance and longer battery life.
When the BTS is installed, if the temperature around the BTS is below 25°C (77°F) the absorb and

fl oat charge voltage increases, and if the temperature around the BTS is higher than 25°C (77°F),

the absorb and fl oat charge voltage decreases. See Figure 3-4

to determine how much the charge

voltage changes (increases or decreases) depending on the temperature reading of the BTS. For

example, the nominal absorb charge voltage for a fl ooded battery at 25°C (77°F) on a 24-volt

model is 29.2 VDC. If the battery temperature is 35°C (95°F), the absorb charge voltage would

decrease to 28.6 VDC (29.2 VDC - 0.6 change).
If the temperature sensor is NOT installed, the charge voltages will not be compensated and the

battery will maintain the charge it had at a temperature of 25°C (77°F). The life of the batteries

may be reduced if they are subjected to large temperature changes when the BTS is not installed.

Info: When the BTS is connected, the battery charger uses a value of 5mV/°C/Cell

from 0-50°C to change the charge voltage based on temperature.

-0.75

-0.6

-0.45

-0.3

-0.15

0

0.15

0.3

0.45

0.6

0.75

0

5

10

15

20

25

30

35

40

45

50

Temperature reading from BTS

Temperature Compensation using BTS

0C

32F

5C

41F

10C

50F

45C

113F

30C

86F

40C

104F

35C

95F

25C

77F

20C

68F

15C

59F

50C

122F

Change to battery charging voltage

no BTS

connected

24VDC units

+1.5V

+1.2V

+0.9V

+0.6V

+0.3V

No Change

-0.3V

-0.6V

-0.9V

-1.2V

-1.5V

48VDC units

+3.0V

+2.4V

+1.8V

+1.2V

+0.6V

No Change

-0.6V

-1.2V

-1.8V

-2.4V

-3.0V

Figure 3-4, BTS Temperature to Charge Voltage Change

This manual is related to the following products: