beautypg.com

6 grounding inverters, Installation 2.6 grounding inverters – Magnum Energy MS-PE Series User Manual

Page 29

background image

Page 22

©

2013 Magnum Energy, Inc.

Installation

2.6 Grounding

Inverters

The inverter/charger should always be properly connected to a permanent, grounded wiring

system. A properly grounded system limits the risk of electrical shock, reduces radio frequency

noise from the inverter, and minimizes excessive surge voltages induced by lightning. Ensure

there is a well-defi ned, low-resistance path from the electrical system to the grounding system.

The low-resistance path helps stabilize the electrical system voltage with respect to ground and

carries fault currents directly to ground if the electrical system malfunctions. Review the following

terms to understand how the conductors in the electrical circuit connect to the system ground:

• Grounded Conductor (GC): The wire/cable in the electrical system that normally carries current

(usually AC neutral and/or DC negative), and is intentionally connected or “bonded” to the ground

system. This wire, or the ends of this wire, should be colored blue.

• Equipment Grounding Conductor (EGC): A wire/cable that does not normally carry current and is

used to connect the exposed metal parts of equipment—that might be accidentally energized—to the

grounding electrode system or to the grounded conductor. This wire, or the ends of this wire, should be

green or green w/yellow stripe; or this wire can be bare copper.

• Grounding Electrode Conductor (GEC): The wire/cable that does not normally carry current and

connects the grounded conductor and/or the equipment grounding conductor to the grounding electrode

at the service equipment.

• Grounding

Electrode

(GE): A ground rod or conducting element that establishes an electrical

connection to the earth.

• System Bonding Jumper (SBJ): The connection between the grounded circuit conductor in the

electrical system and the equipment grounding conductor at a separately derived system.

The MS-PE Series inverter/charger uses both AC and DC power; however, the AC electrical system

is isolated from the DC electrical system by an internal transformer. Although this inverter/charger

has two electrical systems, each electrical system must be properly grounded and connected to

a common earth reference (refer to Figure 2-10).
For proper grounding, each electrical system must connect all exposed metal parts of equipment

(via EGC) and one of the current carrying conductors (GC) together at a common point (ground

busbar – GBB), usually by a system bonding jumper (SBJ) in an electrical service disconnect panel.

The common point of each electrical system is then connected (via GEC) to the common ground

reference, such as a ground rod (GE). This connection to earth should only be made at one point

in each electrical system; otherwise, parallel paths will exist for the currents to fl ow. These parallel

current paths would represent a safety hazard and are to be avoided during installation.

Figure 2-10, Grounding System for MS-PE Series

AC

DC Service

Panel

AC Service

Panel

DC Electrical System

AC Electrical System

Neutral

Positive

Negative

DC

Grounding

System

Negative

SBJ

GC

GE

GEC-AC

EGC

AC Ground

DC Ground

SBJ

EGC

GC

Neutral

Hot

GEC-DC

GE

GE

GBB

GBB

Grounding Electrode

(AC and DC sides shared)

Grounding Electrode

(DC side dedicated)

Grounding Electrode

(AC side dedicated)

or

or

MS-PE Series Inverter/Charger

This manual is related to the following products: