2.5 AC

Wiring

This section provides information on how to make the AC connections to the inverter using the

correct AC wire size and corresponding overcurrent protection.

2.5.1

Pre-AC Wiring Requirements

CAUTION: Before installing any AC wiring, review the safety information at the

beginning of this manual and the following to ensure a safe and long-lived system:
• Always use properly rated circuit breakers. If using an electrical sub-panel, circuit

breakers can be moved from the main electrical panel to the sub-panel only if the

breakers are also listed to be installed in the sub-panel.

• AC wiring must be no less than 5.3 mm

2

(#10 AWG) gauge copper wire and be

approved for the application (i.e., residential, RV, or marine wiring).

• DO NOT connect the inverter’s output to an AC power source. This could cause

severe damage to the inverter and is not covered under warranty.

• The AC wire sizes recommended in this manual are based on the ampacities for

copper wire rated with 75ºC (167ºF) insulation at an ambient temperature of 30ºC

(86ºF).

WARNING: To reduce the risk of fi re, do not connect this inverter to an AC load center

(circuit breaker panel) having multi-wire branch circuits connected.

2.5.2

AC Wire Size and Overcurrent Protection

The AC input and output wiring must be sized per the local electrical safety code requirements

to ensure the wire’s ability to safely handle the inverter’s maximum load current. The AC wiring

must be protected from short circuits and overloads by an overcurrent protection device and have

a means to disconnect the AC circuits. AC overcurrent protection is not included in the inverter

and must be provided as part of the inverter installation. The AC overcurrent protection device

must be a circuit breaker or a fuse/disconnect and be properly sized and branch circuit rated for

the wire it is protecting and the appliances being powered.

Info: When wiring the AC input and output circuits, we highly recommend a full

system Inverter Bypass Switch. This simple item provides a convenient way to isolate

the inverter for battery maintenance, and it could save you hours of downtime—if you

ever need to service your inverter—by enabling you to continue to power your AC loads

without any re-wiring. Because we think it is an essential part of an inverter system,

every Magnum panel (MMP-E/MP-E Series) is equipped with an inverter bypass switch.

When in Standby mode, the full AC continuous pass-thru capacity of the MS-PE Series inverter/

charger is 30 amps. For a 30-amp continuous pass-thru capability, the AC HOT IN input to the

inverter requires a 30-amp continuous duty rated breaker¹, which corresponds to a minimum cable

size of 5.3 mm² (#10 AWG²) in conduit. If you are using other circuit breakers/wire sizes, refer

to the appropriate local electrical codes and standards for proper sizing requirements.

CAUTION: The inverter’s internal AC transfer relay contacts are rated for 30 amps,

the pass-thru current must be no greater than 30 amps or damage to this relay may

occur.

Note¹ The breaker must be de-rated by 80% if not rated for continuous duty. Standard safety

practices require that circuits are not to be operated continuously at more than 80% of rating

unless listed with a 100% continuous rating.

Note² Copper wire rated with 75°C insulation at an ambient temperature of 30°C (86°F).