3.5 Battery Temperature Sensor Operation

The plug-in Battery Temperature Sensor (BTS) is used to determine the battery’s temperature.

This information allows the multi-stage battery charger to automatically adjust the battery charge

voltages for optimum charging performance and longer battery life.
With a BTS installed, if the temperature around the BTS is below 77°F (25°C) the absorb and fl oat

charge voltage increases, and if the temperature around the BTS is higher than 77°F (25°C), the

absorb and fl oat charge voltage decreases. See Figure 3-9

to determine how much the charge

voltage changes (increases or decreases) depending on the temperature reading of the BTS. For

example, the nominal absorb charge voltage for a fl ooded battery at 77°F (25°C) on a 24-volt

model is 29.2 VDC. If the battery temperature is 95°F (35°C), the absorb charge voltage would

decrease to 28.6 VDC (29.2 VDC - 0.6 change).
If the temperature sensor is NOT installed, the charge voltages will not be automatically adjusted

because of temperature, but will be maintained at a temperature of 77°F (25°C). The life of the

batteries may be reduced if they are subjected to large temperature changes when the BTS is

not installed.

Info: When the BTS is connected, the battery charger uses a value of -5mV/°C/Cell

from 0-50°C to change the charge voltage based on temperature.

-0.75

-0.6

-0.45

-0.3

-0.15

0

0.15

0.3

0.45

0.6

0.75

0

5

10

15

20

25

30

35

40

45

50

Temperature reading from BTS

Temperature Compensation using BTS

0C

32F

5C

41F

10C

50F

45C

113F

30C

86F

40C

104F

35C

95F

25C

77F

20C

68F

15C

59F

50C

122F

Change to battery charging voltage

no BTS

connected

12VDC units

+0.75V

+0.6V

+0.45V

+0.3V

+0.15V

No Change

-0.15V

-0.3V

-0.45V

-0.6V

-0.75V

24VDC units

+1.5V

+1.2V

+0.9V

+0.6V

+0.3V

No Change

-0.3V

-0.6V

-0.9V

-1.2V

-1.5V

Figure 3-9, BTS Temperature to Charge Voltage Change