4 ac terminal block connections – Magnum Energy MSH-M Series User Manual

Page 29

background image

Page 20

©

2013 Magnum Energy, Inc.

Installation

CAUTION: GFCIs shall be installed in a recreational vehicle’s wiring system to protect

all branch circuits.

2.5.4

AC Terminal Block Connections

The MSH-M Series models have a four-pole AC terminal block and an AC ground terminal to connect

the inverter’s AC input and output wiring. This terminal block (see Figure 2-8) allows a service/

distribution panel (main panel) to be wired to the inverter’s input, and also allows a dedicated

panel (sub-panel) between the inverter’s output wiring and the AC loads. To access and view the

AC terminal block and ground terminal, remove the two Phillips screws holding the AC wiring access

cover plate (see Item 15, Figure 1-3).
Each connection on the AC terminal block is rated to accept one #14 to #6 AWG (2.1 to 13.3

mm

2

) CU stranded wire, or two #12 AWG (3.3 mm

2

) CU stranded wires. Each connection uses a

M3.5 slotted head screw, and the maximum tightening torque is 16 in lbf (1.8 Nm).

Info: To comply with ABYC requirements for marine installations, the AC terminal has

a stainless steel wire protector to prevent wire damage from the set-screw.

Info: The inverter’s NEUTRAL IN and NEUTRAL OUT terminals are electrically isolated

from each other while inverting. This is related to the neutral-ground bonding

requirement and helps prevent ground-loops (see Section 2.6.5 for more information).

If the installation requires the input and output neutrals to be connected together, the

inverter’s neutral-to-ground connection must be disconnected (see Section 2.6.5).

The AC ground terminal can accept one #14 to #6 AWG (2.1 to 13.3 mm

2

) CU stranded wire. It

uses a slotted head screw and has a recommended maximum tightening torque of 45 in lbf (5.1

N-m).

Figure 2-8, AC Terminal Block

2.5.3

Recommended GFCI (Ground Fault Circuit Interruption) Outlets

Some electrical safety codes require the use of GFCI’s. In compliance with UL standards, Magnum

Energy has tested the following GFCI’s and fi nd that they function properly when connected to

the inverter’s AC output:

• Shock

Sentry

TM

#XGF15V-SP • Leviton Smart Lock #8899-A

• Hubbel

#GF520EMBKA