beautypg.com

1 dc wire sizing, 2 dc overcurrent protection, Installation – Magnum Energy MSH-M Series User Manual

Page 23

background image

Page 14

©

2013 Magnum Energy, Inc.

Installation

2.4.1

DC Wire Sizing

It is important to use the correct sized DC wire to achieve maximum effi ciency from the system

and to reduce fi re hazards associated with overheating. Always keep your wire runs as short as

practical to prevent low voltage shutdowns and to keep the DC breaker from nuisance tripping (or

open fuses) because of increased current draw. See Table 2-1 to select the minimum DC wire size

(and corresponding overcurrent device) required based on your inverter model. The cable sizes

listed in Table 2-1 are required in order to reduce stress on the inverter, minimize voltage drops,

increase system effi ciency, and ensure the inverter’s ability to surge heavy loads.
If the distance from the inverter to the battery bank is >5 feet, the DC wire will need to be increased.

Longer distances cause an increase in resistance, which affects the performance of the inverter.

Use the overcurrent device previously determined from Table 2-1 and then refer to Table 2-2 to

determine the minimum DC wire size needed for various distances, based on your inverter model.

2.4.2

DC Overcurrent Protection

DC overcurrent protection is not included in the inverter—for safety reasons and to comply with

electrical code regulations—it must be provided as part of the installation. The DC overcurrent

protection device must be installed in the positive DC cable line, it can be a fuse or a circuit

breaker and must be DC rated. It must be correctly sized according to the size of DC cables being

used, which means it is required to open before the cable reaches its maximum current carrying

capability, thereby preventing a fi re. In a residential or commercial electrical installation, the NEC

requires both overcurrent protection and a disconnect switch. If a circuit breaker is used as the

overcurrent protection device, it can also be used as the required DC disconnect.
If a fuse is used as an overcurrent device, a Class-T type or equivalent is highly recommended. This

fuse type is rated for DC operation, can handle high short-circuit currents, and has a time delay

that allows for momentary current surges from the inverter without opening the fuse. However,

because the fuse can be energized from both directions, the NEC requires that it be installed in a

manner that the power must be disconnected on both ends of the fuse before servicing.
Use Table 2-1 to select the DC overcurrent device needed based on the recommended minimum

wire size for your particular inverter model (may not meet all local code or NEC requirements).

Table 2-1, Recommended DC Wire/Overcurrent Device for Rated Use

Inverter

Model

Maximum

Continuous

Current

1

Minimum DC Wire Size

(rating)

2

Maximum DC

Fuse Size

3

DC

Grounding

Wire Size

4

MSH3012M

400 amps

#4/0 AWG

(107.2 mm

2

) 405 amps

400 amps

with time delay

#6 AWG

(13.3 mm

2

)

MSH4024M

267 amps

#2/0 AWG

(67.4 mm

2

) 300 amps

300 amps

with time delay

#6 AWG

(13.3 mm

2

)

Note

1

Maximum continuous current is based on the inverter’s continuous power rating at the lowest input

voltage with an inverter ineffi ciency factored in.
Note

2

Copper wire rated with 90°C (194°F) insulation at an ambient temperature of 30°C (86°F), with a

multiple cable fi ll factor (0.8) de-rating in free air (if needed). May require larger conductor, refer to your

application wiring requirements (such as in boats), the DC grounding wire may be required to be the same

ampacity as the positive cable to the inverter.
Note

3

The next larger standard size overcurrent device may be used if the de-rated cable ampacity falls

between the standard overcurrent devices found in the NEC.
Note

4

Per the NEC, the DC grounding electrode conductor can be a #6 AWG conductor if that is the only

connection to the grounding electrode and that grounding electrode is a rod, pipe, or plate electrode.