beautypg.com

4 transfer time, Operation – Magnum Energy MSH-M Series User Manual

Page 43

background image

Page 34

©

2013 Magnum Energy, Inc.

Operation

Figure 3-7, MSH Current Flow – Load Support AAC

MSH Inverter

AC Loads

(Large)

+30A

DC Current

(Battery)

-10A

AC Current

(Grid/Gen)

-20A

Load Support AAC – If AC loads are added that are above the capability of the grid/generator,

the MSH converts current from the battery and combines it with the current from the grid/

generator to power the additional AC loads.

Figure 3-8, MSH Current Flow – Load Support VDC

MSH Inverter

AC Loads

(Large)

+30A

DC Current

(Battery)

-20A

AC Current

(Grid/Gen)

-10A

Load Support VDC – If the battery is being charged externally (i.e., solar, wind, or hydro), the

MSH converts any excess current from the battery to power the AC loads and reduce the current

from the grid/generator.

3.4 Transfer

Time

While in Standby mode, the AC input is continually monitored. Whenever AC power falls below

the VAC dropout voltage (80 VAC, default setting), the inverter automatically transfers back to

Inverter mode with minimum interruption to your appliances—as long as the inverter is turned

on. The transfer from Standby mode to Inverter mode occurs in approximately 16 milliseconds.

While the MSH-M Series is not designed as a computer UPS system, this transfer time is usually

fast enough to hold them up. However, the VAC dropout setting has an effect on the ability of the

loads to transfer without resetting. The lower this setting, the longer the effective transfer will be

and therefore, the higher the probability for the output loads to reset. This occurs because the

incoming AC voltage is allowed to fall to a level that is so low that when the transfer does occur,

the voltage on the inverter’s output has already fallen low enough to reset the loads.
The disadvantage of a higher VAC dropout setting is that smaller generators (or large generators

with an unstable output) may nuisance transfer. This commonly happens when powering loads that

are larger than the generator can handle—causing the generator’s output voltage to constantly

fall below the inverter’s input VAC dropout threshold.

Info: When switching from Inverter mode to Standby mode, the inverter waits

approximately 15 seconds to ensure the AC source is stable before transferring.