Line error
Display

Fault description

LNx_U10M>

Shutdown due to excedance of the voltage

increase protector level 1/level 2 on phase x

(10-minute mean value)

TEST

Button for manual fault triggering has been

activated

System fault
Display

Fault description

RELAYS

Tie circuit-breaker faults: when reading the relay

contacts for the single fault proof assurance, it was

detected that the relay has not been activated

Internal fault
Display

Fault description

VOLTRDC

Internal fault: Difference between the voltage meas-

urement of the 3 phases and the redundant voltage

measurement for the single fault proof assurance

VREF15

Internal fault: in the A/D converter check with refer-

ence voltage for single fault proof assurance, a fault

was detected