A

8.4 RS485 bus

NOTE
Ensure that the DATA+ and DATA- wires are properly

connected. Communication is not possible if the wires are

reversed.

NOTE
Different manufacturers do not always interpret the

standard on which the RS485 protocol is based in the

same way. Note that the wire designations (DATA- and

DATA+) for wires A and B may vary from one manufac-

turer to another.

8.4.1 Specification

Properties of the RS485 data line

Maximum length of

the RS485

bus line

The bus is permitted to be a maximum of

1200m long.

This length can be reached only under opti-

mum conditions.

Cable lengths exceeding 500m generally

require a repeater or a hub.

Maximum number

of bus subscribers

32

Data line

Twisted, shielded. Recommendations:

LI2YCYv (Twisted Pair) black for laying cable

outside and in the ground, 2 x 2 x 0.5

LI2YCY (Twisted Pair) grey for dry and moist

indoor spaces, 2 x 2 x 0.5