Page 21

background image

Page 21

A

1. Connect neutral conductor N

to screw terminal A2

2. Connect the stripped wire

end of the jumper and the AC

supply line to screw terminal A1

»

Connect AC measurement lines

21

22

14

11

12

N

L3

L2

L1

A2

A1

RS485B

RS485A

GND

RS485B

RS485A

GND

CAN H

CAN L

GND

CAN H

CAN L

GND

D01

GND

DI4

DI3

DI2

DI1

24

21

J1J2J3J4

L1

L2

L3

N

L1

L2

L3

N

Figure 4: AC connection

with wire jumper

7.2.2 AC connection without the wire jumper provided

↻ Observe the input voltage

↻ Observe the cable cross-sections

↻ Use a suitable fuse
1. Connect neutral conductor N to

screw terminal A2

2. Connect AC supply line to screw

terminal A1

»

Connect AC measurement lines

21

22

14

11

12

N

L3

L2

L1

A2

A1

RS485B

RS485A

GND

RS485B

RS485A

GND

CAN H

CAN L

GND

CAN H

CAN L

GND

D01

GND

DI4

DI3

DI2

DI1

24

21

J1J2J3J4

L1

L2

L3

N

L1

L2

L3

N

Figure 5: AC connec-

tion without wire

jumper

7.2.3 Connect AC measurement lines
Required to monitor undervoltage, overvoltage, underfrequency and

overfrequency