A

NOTE
Grid failure bridging time
With a supply voltage of 230 V to <50 V, the grid failure

bridging time is 280 ms.
With a supply voltage drop below 100 V, the grid failure

bridging time is 5 s.
An extended undervoltage operation is regarded as improper

usage. An additional fuse of the voltage supply (USV) should

be included in this case.
The grid failure bridging time of the tie circuit-breakers

should be observed. If necessary, the grid connection rule

requires that the tie circuit-breaker is not triggered before the

set trigger delay time.
When using the internal tie circuit-breaker and suitable KACO

inverter, adequate grid failure bridging time must be

provided at all times.

NOTE
If AC-supplied tie circuit-breakers are used, the AC connec-

tion can be simplified.

Use the wire jumper provided to bridge inputs A1, L1, 11

and 21.

Recommended conductor cross-sections and fuse protection of NYM

cables for fixed wiring according to VDE 0100 part 430:

Conductor cross-section: 1.5 mm²

Fuse protection: Automatic circuit breakers, 16 A for 1.5 mm² con-

ductor cross-section