Connecting the ripple control receiver to

the Powador-protect

↻ You have correctly fitted and installed the

ripple control receiver.

↻ Note the control stages! Terminal "1"

(100% nominal power) to terminal "4" (0%

nominal power)

Connect connection leads to the corre-

sponding connection terminals (DI1, DI2,

DI3, DI4, GND).

21

22

14

11

12

N

L3

L2

L1

A2

A1

RS485B

RS485A

GND

RS485B

RS485A

GND

CAN H

CAN L

GND

CAN H

CAN L

GND

D01

GND

DI4

DI3

DI2

DI1

24

21

J1J2J3J4

Figure 9: Ripple

control

receiver

Configure Powador-protect for ripple control receiver

↻ Observe the grid operator specifications!
1. Open menu level 3.
2. Change "Pwr-Ctr active" option to "Yes".
3. Configure 4 control stages "Pwr-Ctr Dl1" to "Pwr-Ctr Dl4" and

option "Pwr-Ctr All Dl".

If no ripple control receiver is connected to the device, the option

"Pwr-Ctr active" should be set to "No".
8.2.2 Connect signal sources for remote shutdown and fre-

quency limitation
to monitor undervoltage, overvoltage, underfrequency and overfre-

quency.
Country setting: "IT-CEI021"