Connecting the ripple control receiver to
the Powador-protect
↻ You have correctly fitted and installed the
ripple control receiver.
↻ Note the control stages! Terminal "1"
(100% nominal power) to terminal "4" (0%
nominal power)
�
Connect connection leads to the corre-
sponding connection terminals (DI1, DI2,
DI3, DI4, GND).
21
22
14
11
12
N
L3
L2
L1
A2
A1
RS485B
RS485A
GND
RS485B
RS485A
GND
CAN H
CAN L
GND
CAN H
CAN L
GND
D01
GND
DI4
DI3
DI2
DI1
24
21
J1J2J3J4
Figure 9: Ripple
control
receiver
Configure Powador-protect for ripple control receiver
↻ Observe the grid operator specifications!
1. Open menu level 3.
2. Change "Pwr-Ctr active" option to "Yes".
3. Configure 4 control stages "Pwr-Ctr Dl1" to "Pwr-Ctr Dl4" and
option "Pwr-Ctr All Dl".
If no ripple control receiver is connected to the device, the option
"Pwr-Ctr active" should be set to "No".
8.2.2 Connect signal sources for remote shutdown and fre-
quency limitation
to monitor undervoltage, overvoltage, underfrequency and overfre-
quency.
Country setting: "IT-CEI021"