8.4.2 Connecting the RS485 bus

NOTE

To prevent interference during data transmission:

Observe the wire twisted pairing when connecting

DATA+ and DATA- (see Figure 12)

Do not install RS485 bus lines in the vicinity of live

DC/AC cables.

1. Connect the connection cable to the cor-

responding connection terminals.

2. Connect in this manner to all bus sub-

scribers

Wire A (-) with wire A (-) and

Wire B (+) with wire B (+).

Optional: Place screen of the connec-

tion cable on terminal GND.

3. If terminal unit: activate the terminating

resistor.

Figure 12: Wire

twisted-pair

connection

NOTE
When using compatible inverters, the RS485 cabling

can also be laid via the RJ45 socket to the underside

of the device. The connection terminals can also be

used together with the RJ45 socket, for example with

combined use of Powador-protect, inverters with RJ45

socket and proLOG.