KACO Powador-protect User Manual
Page 41
Page 41
A
Display
Action in this menu/meaning
2-stage params
Enable:
Permit setting of the shutdown limits for shut-
down level 2
Disable:
Prohibit setting of the shutdown limits for
shutdown level 2
U>: val, Toff
Set limit value voltage increase protector and
trigger delay time for level 1/level 2 shutdown
U>>: val, Toff
UR>
Set reconnection threshold after overvoltage
shutdown
U<: val, Toff
Set limit value voltage drop protector and
trigger delay time for level 1/level 2 shutdown
U<<: val, Toff
UR<
Set reconnection threshold after
undervoltage shutdown
U10M>: val,
Toff
Set limit value voltage increase protector for
shutdown due to 10-minute mean value
F>: val, Toff
Set limit value frequency increase protec-
tor and trigger delay time for level 1/level 2
shutdown
F>>: val, Toff
FR>
Set reconnection threshold after overfre-
quency shutdown
F<: val, Toff
Set limit value frequency drop protector and
trigger delay time for level 1/level 2 shutdown
F<<: val, Toff
FR<
Set reconnection threshold after underfre-
quency shutdown