A

Display

Action in this menu/meaning

Tstart

Time of grid monitoring up to

connection after device restart (in s)

Twait

Time of grid monitoring up to

re-connection after fault triggering (in s)

Clear log

"Yes": delete saved log data
"No": no action

U

nom

Set nominal voltage of the monitored public

power grid

Remote

tripping

"Active high": The "Remote shutdown" func-

tion becomes active when digital input DI1

(RMT) is connected to GND.
"Active low": The "Remote shutdown" function

becomes active when digital input DI1 (RMT)

is open.

Inv-off signal

"Interface switch": Digital output DO1

switches the connected inverters off when

relay 1 opens.
"Backup device": Digital output DO1 switches

the connected inverters off when relay 2

opens.

Relay loop-

back

"Active high":

The tie circuit-breakers are closed when digi-

tal input 4 (IFS)

is connected to GND.
"Active low":

The tie circuit-breakers are closed when digi-

tal input 4 (IFS) is open.