KACO Powador-protect User Manual
Page 38
Page 38
A
Display
Action in this menu/meaning
RS485 role
Set role of the Powador-protect in the RS485
bus
Master: no proLOG is used,
Powador-protect is the terminal unit
Slave: proLOG is used, Powador-
protect is bus subscriber or terminal unit
Observe the bus termination!
RS485 address
Assign unique RS485 bus address (1...31)
U
nom
Nominal voltage of the monitored
public power grid
U>: val, Toff
Limit value voltage increase protector and trig-
ger delay time for level 1/level 2 shutdown
U>>: val, Toff
UR>
Reconnection threshold after
overvoltage shutdown
U<: val, Toff
Limit value voltage drop protector and trigger
delay time for level 1/level 2 shutdown
U<<: val, Toff
UR<
Reconnection threshold after
undervoltage shutdown
U10M>: val,
Toff
Limit value voltage increase protector for shut-
down due to 10-minute mean value
F>: val, Toff
Limit value frequency increase protector and
trigger delay time for level 1/level 2 shutdown
F>>: val, Toff
FR>
Reconnection threshold after
overvoltage shutdown