Supply

Contact load capacity on the Powador-protect

AC

250 V / 2 A inductive

DC

24 V / 8 A

Connect AC supplied tie circuit-breaker (Figure 7)

↻ You have installed 2 suitable external tie circuit-breakers

between feed-in meter and generation plant.

1. Connect "A1" connection of tie circuit-breaker 1 to terminal "14"

of the Powador-protect.

2. Connect "A2" connection of tie circuit-breaker 1 to neutral con-

ductor N of the AC voltage supply.

3. Connect terminal "11" of the Powador-protect to a phase of the

AC voltage supply.

The connection of tie circuit-breaker 2 is made on the same

principle (A1 to "24", A2 to "N", L1 to "21").