A

Connecting the DC-supplied tie circuit-breaker (Figure 8)

↻ You have installed 2 suitable external tie circuit-breakers

between feed-in meter and generation plant.

1. Connect "A1" connection of tie circuit-breaker 1 to terminal 14

of the Powador-protect.

2. Connect "A2" connection of tie

circuit-breaker 1 to the minus pole

of the DC voltage supply.

3. Connect plus pole of the DC

supply to terminal "11" of the

Powador-protect.

The connection of tie circuit-

breaker 2 is made on the same

principle

(A1 to "24", A2 to DC-, DC+ to "21").

21

22

14

11

12

24

21

L1

L2

L3

N

Figure 8: DC-supplied

tie circuit-breaker

8.2 Digital inputs
8.2.1 Connect ripple control receiver
for feed management by the power supply company.
Country settings: "Germany", "Power Control", "User Defined"
Observe the installation and operating regulations of the ripple con-

trol receiver.

NOTE
The Powador-protect has an individual GND connec-

tion. A bridging of the GND connection of the ripple

control receiver can therefore be required outside the

device.