Connecting the DC-supplied tie circuit-breaker (Figure 8)
↻ You have installed 2 suitable external tie circuit-breakers
between feed-in meter and generation plant.
1. Connect "A1" connection of tie circuit-breaker 1 to terminal 14
of the Powador-protect.
2. Connect "A2" connection of tie
circuit-breaker 1 to the minus pole
of the DC voltage supply.
3. Connect plus pole of the DC
supply to terminal "11" of the
Powador-protect.
�
The connection of tie circuit-
breaker 2 is made on the same
principle
(A1 to "24", A2 to DC-, DC+ to "21").
21
22
14
11
12
24
21
L1
L2
L3
N
Figure 8: DC-supplied
tie circuit-breaker
8.2 Digital inputs
8.2.1 Connect ripple control receiver
for feed management by the power supply company.
Country settings: "Germany", "Power Control", "User Defined"
Observe the installation and operating regulations of the ripple con-
trol receiver.
NOTE
The Powador-protect has an individual GND connec-
tion. A bridging of the GND connection of the ripple
control receiver can therefore be required outside the
device.