A

21

22

14

11

12

N

L3

L2

L1

A2

A1

D01

GND

DI4

DI3

DI2

DI1

24

21

L1

L2

L3

N

L1

L2

L3

N

Figure 10: AC tie circuit-breaker; signal sources for remote shutdown

and frequency limitation

DI1: Remote shutdown
1. Connect connection leads of the signal source for the remote

shutdown to connection terminals DI1 and GND.

2. After commissioning: Configure "Remote tripping" setting.

DI2/DI3: Frequency shutdown limits

Connect connection leads of the first signal source for the fre-

quency shutdown limits to connection terminals DI1 and GND.

Connect connection leads of the second signal source for the

remote shutdown to connection terminals DI3 and GND.

NOTE
Whilst one of the two inputs DI2 or DI3 is connected to

GND, the other frequency shutdown limits are active.

Otherwise the tight frequency shutdown limits are active.