3.3 Drive Mode Indicators
60
YASKAWA TM.iQp.06 iQpump Controller User Manual
3.3
Drive Mode Indicators
The definitions of the iQpump drive mode indicators are shown in
.
Table 3.2 iQpump Drive Mode Indicators
◆ AUTO Sequence (SEQ) Indicator
The status of the AUTO “Sequence” (SEQ) indicator is shown in
. This indicator is always “Off” when the iQpump drive is in
the “Hand” mode. When the iQpump drive is in the “Auto” mode, the SEQ indicator status is dependent on the setting of parameter
“b1-02” (Run Command Selection).
Table 3.3 AUTO Sequence (SEQ) Indicator
The status of the AUTO “Reference” (REF) indicator is shown in
. This indicator is always “Off” when the iQpump drive is in
the “Hand” mode. When the iQpump drive is in the “Auto” mode, the REF indicator status is dependent on the setting of parameter
“b1-01” (Frequency Reference Selection).
Table 3.4 AUTO Reference (REF) Indicator
◆ Run Indicator
The status of the “RUN” indicator is shown in
when the iQpump drive is in either the “Hand” or “Auto” mode.
Table 3.5 RUN Indicator
Indicator
Definition
FWD
Lit when a forward run command is input and when drive is in “Hand” Mode.
AUTO SEQ
Lit when set up for remote run command. See
AUTO REF
Lit when set up for remote speed command. See
.
ALARM
Lit when a fault has occurred. Flashes when an alarm has occurred.
Indicator Status
Hand Mode
Auto Mode
On
N/A
Parameter “b1-02” (Run Command Selection) is set to terminal strip, communications, or
an option board as indicated below:
b1-02= 1 (Terminals)
= 2 (Communications)
= 3 (Option PCB)
Off
Parameter “b1-02” (Run Command Selection) is set to digital operator as indicated below:
b1-02 = 0 (Operator)
Indicator Status
Hand Mode
Auto Mode
On
N/A
Parameter “b1-01” (Frequency Reference Selection) is set to terminal strip,
communications, or an option board as indicated below:
b1-01= 1 (Terminals)
= 2 (Communications)
= 3 (Option PCB)
Off
Parameter “b1-01” (Frequency Reference Selection) is set to digital operator as indicated
below:
b1-01= 0 (Operator)
Indicator Status
Condition
On
Drive is running
Blinking
Drive is decelerating to a stop
Off
Drive is stopped