5 heat loss data, Heat loss data – Yaskawa iQpump Controller User Manual User Manual
Page 27

1.5 Heat Loss Data
YASKAWA TM.iQp.06 iQpump Controller User Manual
27
1.5
Heat Loss Data
Table 1.3 200V Class Heat Loss Data
Table 1.4 400V Class Heat Loss Data
TYPE
CIMR-P7U-107
Drive
(Inverter)
Capacity
(kVA)
Rated
Output
Current
(A)
Cooling Fin Side
(W)
Internal
Unit Side (W)
Total
Watt Loss
(W)
Cooling Method
20P4
1.4
3.6
19
39
58
Self
20P7
1.8
4.6
26
42
68
Self
21P5
3.0
7.8
48
50 98
Self
22P2
4.1
10.8
68
59
127
Self
23P7
6.4
16.8
110
74
184
Fan
25P5
8.8
23
164
84
248
Fan
27P5
12
31
219
113
332
Fan
2011
18
46.2
357
168
524
Fan
2015
23
59.4
416
182
597
Fan
2018
29
74.8
472
208
680
Fan
2022
34
88
583
252
835
Fan
2030
44
115
883
333
1217
Fan
2037
62
162
1010
421
1430
Fan
2045
73
192
1228
499
1727
Fan
2055
82
215
1588
619
2206
Fan
2075
120
312
1956
844
2800
Fan
2090
140
360
2194
964
3157
Fan
2110
160
415
2733
1234
3967
Fan
TYPE
CIMR-P7U-107
Drive
(Inverter)
Capacity
(kVA)
Rated
Output
Current
(A)
Cooling Fin Side
(W)
Internal
Unit Side (W)
Total
Watt Loss
(W)
Cooling Method
40P4
1.4
1.8
14
39
53
Self
40P7
1.6
2.1
17
41
58
Self
41P5
2.8
3.7
36
48 84
Self
42P2
4.0
5.3
59
56
115
Fan
43P7
5.8
7.6
80
68
140
Fan
44P0
6.6
8.7
90
70
160
Fan
45P5
9.5
12.5
127
81
209
Fan
47P5
13
17
193
114
307
Fan
49P0
16
21
232
158
390
Fan
4011
21
27
232
158
390
Fan
4015
26
34
296
169
465
Fan
4018
30
40
389
201
590
Fan
4022
38
50.4
420
233
653
Fan
4024
40
52
691
297
989
Fan
4030
51
67.2
691
297
989
Fan
4037
59
77
801
332
1133
Fan
4045
73
96
901
386
1287
Fan
4055
95
125
1204
478
1682
Fan
4075
120
156
1285
562
1847
Fan
4090
140
180
1614
673
2287
Fan
4110
180
240
1889
847
2736
Fan
4132
200
260
2388
1005
3393
Fan
4160
230
304
2636
1144
3936
Fan
4185
315
414
2791
1328
3964
Fan
4220
390
515
3797
1712
5509
Fan
4300
510
675
5838
2482
8319
Fan