2 digital operator keys, Digital operator keys – Yaskawa iQpump Controller User Manual User Manual
Page 59

3.2 Digital Operator Keys
YASKAWA TM.iQp.06 iQpump Controller User Manual
59
3.2
Digital Operator Keys
The names and functions of the digital operator Keys are described in
Table 3.1 Digital Operator Keys
Key
Name
Function
AUTO Key
• Pressing the AUTO key will put the drive in the “Auto” mode.
• In the “Auto” mode, the drive will be capable of starting / stopping depending on the setting of parameter
“b1-02” (Run Command Selection).
• In the “Auto” mode, the drive setpoint will depend on the setting of parameter “b1-01” (Reference Source).
• If the OFF key is pressed, the “Auto” mode frequency reference will continue to be displayed on the keypad.
• Pressing the AUTO key will start the drive if the run command is already closed.
• If the drive is running in the “Auto” mode and the OFF key is pressed, the drive will stop. If the run command
remains closed, pressing the AUTO key will restart the drive.
• While the drive is running, the run command can be opened to stop and closed to restart without taking the
drive out of the “Auto” mode.
MENU Key
Scrolls through the five main menus.
ESCAPE Key
Returns to the previous display, before the DATA / ENTER key was pressed.
MONITOR Key
Selects the monitor mode from the Operation (-DRIVE-), Quick Setting (-QUICK-), Programming (-ADV-) and
Modified Constants (-VERIFY-) menus + A.TUNE.
INCREASE Key
Increases parameter numbers and set values.
Used to move to the next item or data value.
DECREASE Key
Decreases parameter numbers and set values.
Used to move to the previous item or data value.
SHIFT / RESET Key
Selects the digit to be changed. The selected digit will blink.
Also resets the drive when a fault has occurred, if the fault condition doesn’t exist anymore and there isn’t an
active RUN command.
DATA / ENTER Key
Pressed to enter menus and parameters as well as to set values.
HAND Key
• Pressing the HAND key will put the drive in the “Hand” mode and start the drive.
• In the “Hand” mode, the drive speed command will depend on the setting of parameter “P5-01” (Hand Mode
Source and P5-02 Hand Reference).
• If the OFF key is pressed, the “Hand” mode speed command will continue to be displayed on the keypad.
OFF Key
Stops drive operation, following the stopping method as programmed in parameter b1-03.