Connect level transducer to the iqpump drive – Yaskawa iQpump Controller User Manual User Manual
Page 242

242
YASKAWA
TM.iQp.06 iQpump Controller User Manual
G.3 Well Draw Down Function
■
3. Connect Level Transducer to the iQpump Drive
Most depth level transducers provide a 4 ~ 20 mA current signal. The A1 Terminal of the iQpump drive is calibrated for voltage-based
feedback at 0 ~ 10 Vdc. Installing a burden resistor simplifies the process of converting the current-based feedback to voltage-based
feedback.
The burden resistor should be 250 Ohms rated for a minimum of 1/4 W and a tolerance range of less than or equal to 1%. It is possible to
use different Ohm values if a burden resistor of exactly 250 Ohms is not available, however the gain and bias settings of the iQpump
drive must be adjusted accordingly.
Resistors can be purchased at most electronic stores, online, or through catalogues. Locate the necessary resistor value in
below and match that to the correct gain (H3-02) and bias (H3-03) setting for that value.
Table G.2 Resistor Values and Gain/Bias Settings
The burden resistor is installed onto drive Terminal A1 to AC (analog common) see
.
Gain Setting
Bias Setting
Gain Setting
Bias Setting
Ohms
H3-02
H3-03
Ohms
H3-02
H3-03
230
251.4%
-27.2%
250
231.3%
-25.0%
231
250.3%
-27.1%
251
230.3%
-24.9%
232
249.2%
-26.9%
252
229.4%
-24.8%
233
248.1%
-26.8%
253
228.5%
-24.7%
234
247.1%
-26.7%
254
227.6%
-24.6%
235
246.0%
-26.6%
255
226.7%
-24.5%
236
245.0%
-26.5%
256
225.8%
-24.4%
237
243.9%
-26.4%
257
225.0%
-24.3%
238
242.9%
-26.3%
258
224.1%
-24.2%
239
241.9%
-26.2%
259
223.2%
-24.1%
240
240.9%
-26.0%
260
222.4%
-24.0%
241
239.9%
-25.9%
261
221.5%
-23.9%
242
238.9%
-25.8%
262
220.7%
-23.9%
243
237.9%
-25.7%
263
219.8%
-23.8%
244
236.9%
-25.6%
264
219.0%
-23.7%
245
236.0%
-25.5%
265
218.2%
-23.6%
246
235.0%
-25.4%
266
217.3%
-23.5%
247
234.1% -25.3%
267
216.5%
-23.4%
248
233.1%
-25.2%
268
215.7%
-23.3%
249
232.2%
-25.1%
269
214.9%
-23.2%
This table is valid for 4-20 mA feedback devices only.
Use 1/4 W resistors with a tolerance of 1%.