D.3 Modbus Data Tables
002B
Sequence input status
Bit 0
Input terminal S1 1: ON 0: OFF
Bit 1
Input terminal S2 1: ON 0: OFF
Bit 2
Multi-function digital input terminal S3 1: ON 0: OFF
Bit 3
Multi-function digital input terminal S4 1: ON 0: OFF
Bit 4
Multi-function digital input terminal S5 1: ON 0: OFF
Bit 5
Multi-function digital input terminal S6 1: ON 0: OFF
Bit 6
Multi-function digital input terminal S7 1: ON 0: OFF
Bits 7 to F
Not used
002C
Drive status
Bit 0
Operation 1: Operating
Bit 1
Zero speed 1: Zero speed
Bit 2
Frequency agree 1: Matched
Bit 3
Desired frequency agree 1: Matched
Bit 4
Frequency detection 1 1: Output frequency
≤ L4-01
Bit 5
Frequency detection 2 1: Output frequency
≥ L4-01
Bit 6
Drive startup completed 1: Startup completed
Bit 7
Low voltage detection 1: Detected
Bit 8
Baseblock 1: Drive output baseblock
Bit 9
Frequency reference mode 1: Not communication 0: Communication
Bit A
Run command mode 1: Not communication 0: Communication
Bit B
Overtorque detection 1: Detected
Bit C
Frequency reference lost 1: Lost
Bit D
Retrying error 1: Retrying
Bit E
Error (including Modbus communications time-out) 1:Error occurred
Bit F
Modbus communications time-out 1: Timed out
002D
Multi-function digital output status
Bit 0
Multi-function digital output 1 (terminal M1-M2) 1: ON 0: OFF
Bit 1
Multi-function digital output 2 (terminal M3-M4): 1: ON 0: OFF
Bit 2
Not used
Bits 3 to F
Not used
002E - 0030
Not used
0031
Main circuit DC voltage
0032 - 0037
Not used
0038
PI feedback level (Input equivalent to 100 % / Max. output frequency; 10/1%; without sign)
0039
PI input level (±100%/±Max. output frequency; 10/1 %; with sign)
003A
PI output level (±100%/±Max. output frequency; 10/1 %; with sign)
003B
CPU software number
003C
Flash software number
003D
Communication error details
Bit 0
CRC error
Bit 1
Invalid data length
Bit 2
Not used
Bit 3
Parity error
Bit 4
Overrun error
Bit 5
Framing error
Bit 6
Time-out
Bits 7 to F
Not used
003E
KVA setting
003F
Control method
Note: Communication error details are stored until an error reset is input (errors can be reset while the drive is operating).
Register No.
(Hex)
Contents