D.2 modbus function code details, Modbus function code details, Reading / holding register contents (03h) – Yaskawa iQpump Controller User Manual User Manual
Page 218: Write in single holding register (06h)

218
YASKAWA
TM.iQp.06 iQpump Controller User Manual
D.2 Modbus Function Code Details
D.2 Modbus Function Code Details
◆ Reading / Holding Register Contents (03H)
Read the contents of the storage register only for specified quantities. The addresses must be consecutive, starting from a specified
address. The data content of the storage register are separated into higher 8 bits and lower 8 bits.
The following table shows message examples when reading status signals, error details, data link status, and frequency references from
the slave 2 drive.
Figure D.6 Function Code 03 H Message Example
◆ Write In Single Holding Register (06H)
Figure D.7 Function Code 06 H Message Example
Command Message
Response Message
(During Normal Operation)
Response Message
(During Error)
Slave Address
02 H
Slave Address
02 H
Slave Address
02 H
Function Code
03 H
Function Code
03 H
Function Code
83 H
Start Address
Higher
00 H
Data quantity
08 H
Error code
03 H
Lower
20 H
1st storage
register
Higher
00 H
CRC-16
Higher
F1 H
Quantity
Higher
00 H
Lower
65 H
Lower
31 H
Lower
04 H
Next storage
register
Higher
00 H
CRC-16
Higher
45 H
Lower
00 H
Lower
F0 H
Next storage
register
Higher
00 H
Lower
00 H
Next storage
register
Higher
01 H
Lower
F4 H
CRC-16
Higher
AF H
Lower
82 H
Command Message
Slave address
01 H
Function code
06 H
Upper 00
H
Register
Address
Lower 01
H
Upper 00
H
Setting
Data
Lower 03
H
Upper 98
H
CRC-16
Lower 0B
H
Response Message
(During Normal Operation)
Slave address
01 H
Function code
06 H
Upper 00
H
Register
Address
Lower 01
H
Upper 00
H
Setting
Data
Lower 03
H
Upper 98
H
CRC-16
Lower 0B
H
Response Message
(During Error)
Slave address
01 H
80H + Function Code
86 H
Error code
21 H
Upper 82
H
CRC-16
Lower 78
H