SMA STP 10000TL-10 Installation User Manual
Page 97

SMA Solar Technology AG
14 Technical Data
Installation Manual
STP10-17TL-IA-en-32
97
AC Output
* Depending on country setting
Protective Devices
Rated power at 230 V, 50 Hz
12,000 W
Maximum apparent AC power cos φ = 1
12,000 VA
Rated grid voltage
3/N/PE, 230 V/400 V
AC voltage range*
160 V to 280 V
Nominal AC current at 230 V
17.4 A
Maximum output current
19.2 A
Maximum output current in the event of an error
0.05 kA
Total harmonic factor of output current at
AC voltage < 2% and AC power > 0.5% of
nominal AC power
≤ 3.6%
Maximum residual output current
96 mA
Rated mains frequency
50 Hz
AC mains frequency*
50 Hz/60 Hz
Operating range at AC mains frequency 50 Hz
44 Hz to 55 Hz
Operating range at AC mains frequency 60 Hz
54 Hz to 65 Hz
Displacement power factor, adjustable
0.8
overexcited
to 1 to 0.8
underexcited
Feed-in phases
3
Connection phases
3
Overvoltage category as per IEC 60664-1
III
DC reverse polarity protection
Short-circuit diode, electronic string fuse
Protection against module reverse currents
Electronic string fuse
Input-side disconnection device
Electronic Solar Switch, SUNCLIX DC connector
DC overvoltage protection
Thermally monitored varistors
optional: surge arrester type II
AC short-circuit current capability
Current control
Grid monitoring
SMA Grid Guard 4
Maximum permissible fuse protection
50.0 A
Earth fault monitoring
Insulation monitoring R
iso
> 458.7 k Ω
All-pole sensitive residual-current monitoring unit
available
String-failure detection
available