2 cleaning the fan at the bottom of the inverter, Stp 15000tl and stp 17000tl only) – SMA STP 10000TL-10 Installation User Manual
Page 67
SMA Solar Technology AG
10 Maintenance and Cleaning
Installation Manual
STP10-17TL-IA-en-32
67
10.2.2 Cleaning the Fan at the Bottom of the Inverter
(STP 15000TL and STP 17000TL only)
1. Disconnect the inverter (see Section 9 "Disconnecting the Inverter from Voltage Sources",
2. Wait for the fan to stop rotating.
Cleaning the Fan Guards
3. To dismantle the fan guard:
– Use a screwdriver to press both latches at the
right edge of the fan guard to the right and
dislodge it from the retainer.
– Carefully remove the fan guard.
4. Clean the fan guard with a soft brush, a paint brush, a cloth or compressed air.
Cleaning the Fans
5. Press the latches in towards the centre.
6. Remove the fan by pulling it slowly and carefully
downwards.
7. Release and remove the plug.
The fan cables are long enough to let you lift the fan
out sufficiently to disconnect the plugs inside the
inverter.
8. Remove the fan and clean it with a soft brush, a paint brush or a cloth and water.
Damage to the fan through use of compressed air
• Do not use compressed air to clean it. This could damage the fan.