14 technical data, 1 sunny tripower 10000tl – SMA STP 10000TL-10 Installation User Manual
Page 92
14 Technical Data
SMA Solar Technology AG
92
STP10-17TL-IA-en-32
Installation Manual
14 Technical Data
14.1 Sunny Tripower 10000TL
DC Input
* To be observed in the event of short-circuit of the electronic string fuse
AC Output
Maximum DC power at cos φ = 1
10,200 W
Maximum input voltage
1,000 V
MPP voltage range
320 V to 800 V
Rated input voltage
600 V
Minimum input voltage
150 V
Initial input voltage
188 V
Maximum feedback current
2 A
Maximum input current, input A
22.0 A
Maximum input current, input B
11.0 A
Maximum input current per string input A*
33.0 A
Maximum input current per string input B*
12.5 A
Number of independent MPP inputs
2
Strings per MPP input, input A
4
Strings per MPP input, input B
1
Rated power at 230 V, 50 Hz
10,000 W
Maximum apparent AC power cos φ = 1
10,000 VA
Rated grid voltage
3/N/PE, 230 V/400 V
AC voltage range*
160 V to 280 V
Nominal AC current at 230 V
14.5 A
Maximum output current
16.0 A
Maximum output current in the event of an error
0.05 kA
Total harmonic factor of output current at
AC voltage < 2% and AC power > 0.5% of
nominal AC power
≤ 3%
Maximum residual output current
96 mA