3 sunny tripower 15000tl – SMA STP 10000TL-10 Installation User Manual
Page 101

SMA Solar Technology AG
14 Technical Data
Installation Manual
STP10-17TL-IA-en-32
101
14.3 Sunny Tripower 15000TL
DC Input
* To be observed in the event of short-circuit of the electronic string fuse
AC Output
Maximum DC power at cos φ = 1
15,340 W
Maximum input voltage
1,000 V
MPP voltage range
360 V to 800 V
Rated input voltage
600 V
Minimum input voltage
150 V
Initial input voltage
188 V
Maximum feedback current
2 A
Maximum input current, input A
33.0 A
Maximum input current, input B
11.0 A
Maximum input current per string input A*
40.0 A
Maximum input current per string input B*
12.5 A
Number of independent MPP inputs
2
Strings per MPP input, input A
5
Strings per MPP input, input B
1
Rated power at 230 V, 50 Hz
15,000 W
Maximum apparent AC power cos φ = 1
15,000 VA
Rated grid voltage
3/N/PE, 230 V/400 V
AC voltage range*
160 V to 280 V
Nominal AC current at 230 V
21.7 A
Maximum output current
24.0 A
Maximum output current in the event of an error
0.05 kA
Total harmonic factor of output current at
AC voltage < 2% and AC power > 0.5% of
nominal AC power
≤ 3.0%
Maximum residual output current
96 mA
Rated mains frequency
50 Hz
AC mains frequency*
50 Hz/60 Hz