4 sunny tripower 17000tl – SMA STP 10000TL-10 Installation User Manual
Page 105

SMA Solar Technology AG
14 Technical Data
Installation Manual
STP10-17TL-IA-en-32
105
Grid Configuration
Data Storage Capacity
Efficiency
14.4 Sunny Tripower 17000TL
DC Input
* To be observed in the event of short-circuit of the electronic string fuse
TN-C network
suitable
TN-S network
suitable
TN-C-S network
suitable
TT grid
suitable
Daily energy yield performance
63 days
Daily yields
30 years
Event messages for users
250 events
Event messages for installers
250 events
Maximum efficiency, η
max
98.2%
European weighted efficiency, η
EU
97.8%
Maximum DC power at cos φ = 1
17,410 W
Maximum input voltage
1,000 V
MPP voltage range
400 V to 800 V
Rated input voltage
600 V
Minimum input voltage
150 V
Initial input voltage
188 V
Maximum feedback current
2 A
Maximum input current, input A
33.0 A
Maximum input current, input B
11.0 A
Maximum input current per string input A*
40.0 A
Maximum input current per string input B*
12.5 A
Number of independent MPP inputs
2
Strings per MPP input, input A
5
Strings per MPP input, input B
1