SMA STP 10000TL-10 Installation User Manual
Page 103
SMA Solar Technology AG
14 Technical Data
Installation Manual
STP10-17TL-IA-en-32
103
* VDE-AR-N-4105: valid from Firmware Version 2.31. Setting in accordance with VDE-ARN-4105 (Germany)
NRS 97-2-1: This standard stipulates that a special sticker be attached to the AC distribution to draw attention to the AC-side
disconnection of the inverter in case of grid failure (for more details, see NRS 97-2-1, Sec. 4.2.7.1 and 4.2.7.2)
C10/11: Only possible if the three-phase nominal voltage of the phase conductor is 400 V
EN 50438: Does not apply to all country standard deviations of EN 50438.
IEC 62109-2: This standard requires either that the multi-function relay is used as a fault indicator or that the inverter is registered
with the Sunny Portal and the error alarm is activated in the Sunny Portal.
Climatic Conditions in Accordance with IEC 60721-3-4, Installation Type C,
Class 4K4H
Climatic Conditions in Accordance with IEC 60721-3-4, Transport Type E,
Class 2K3
Maximum permissible value for relative humidity,
non-condensing
100%
Maximum operating altitude above MSL
3,000 m
Power loss in night mode
< 1 W
Topology
transformerless
Cooling concept
OptiCool: temperature-controlled fan
Fan connection
designed for safe disconnection according to
DIN EN 50178:1998-04
Degree of protection according to IEC 60529
IP65
Protection class (according to IEC 62103)
I
Country standards, as of 04/2013*
VDE-AR-N4105, VDE 0126-1-1, AS4777,
C10/11, PPDS, GBT19939-2005,
UTE C15-712-1, PPC, NRS 97-2-1, EN50438,
RD661/2007, IEC 61727, G59/2, CEI 0-21,
BDEW 2008, RD1699:2011, SI4777,
NEN EN 50438, DIN EN 62109-1,
IEC 62109-2
Extended temperature range
− 25°C to +60°C
Extended humidity range
0% to 100%
Extended air pressure range
79.5 kPa to 106 kPa
Temperature range
− 25°C to +70°C