SMA STP 10000TL-10 Installation User Manual
Page 93
SMA Solar Technology AG
14 Technical Data
Installation Manual
STP10-17TL-IA-en-32
93
* Depending on country setting
Protective Devices
General Data
Rated mains frequency
50 Hz
AC mains frequency*
50 Hz/60 Hz
Operating range at AC mains frequency 50 Hz
44 Hz to 55 Hz
Operating range at AC mains frequency 60 Hz
54 Hz to 65 Hz
Displacement power factor, adjustable
0.8
overexcited
to 1 to 0.8
underexcited
Feed-in phases
3
Connection phases
3
Overvoltage category as per IEC 60664-1
III
DC reverse polarity protection
Short-circuit diode, electronic string fuse
Protection against module reverse currents
Electronic string fuse
Input-side disconnection device
Electronic Solar Switch, SUNCLIX DC connector
DC overvoltage protection
Thermally monitored varistors
optional: surge arrester type II
AC short-circuit current capability
Current control
Grid monitoring
SMA Grid Guard 4
Maximum permissible fuse protection
50.0 A
Earth fault monitoring
insulation monitoring R
iso
> 550 k Ω
All-pole sensitive residual-current monitoring unit
available
String-failure detection
available
Width x height x depth with
Electronic Solar Switch
665 mm x 690 mm x 265 mm
Weight
59 kg
Length x width x height of packaging
780 mm x 380 mm x 790 mm
Transport weight
65 kg
Climatic class in accordance with
IEC 60721-3-4
4K4H
Environment category
Outdoors
Degree of pollution outside the enclosure
3
Degree of pollution inside the enclosure
2