beautypg.com

SMA STP 10000TL-10 Installation User Manual

Page 64

background image

9  Disconnecting the Inverter from Voltage Sources

SMA Solar Technology AG

64

STP10-17TL-IA-en-32

Installation Manual

10. Release and disconnect all DC connectors.

To do this, insert a flat-blade screwdriver
(blade width: 3.5 mm) into one of the side slots and
pull the DC connectors out straight.
Do NOT PULL ON THE CABLE.
☑ All DC connectors are disconnected from the

inverter. The inverter is completely disconnected
from the PV array.

☑ The inverter is now voltage-free and work can be carried out.

Danger to life due to high voltages in the inverter
There is residual voltage in the inverter. The inverter takes 20 minutes to discharge.

• Wait 20 minutes before you open the upper enclosure lid or the DC lid.

This manual is related to the following products: