SMA SI-TB-BOX-10 User Manual
Page 69

SMA America, LLC
14 Technical Data
Installation Manual
SI_TDBOX-IA-eng-IUS122211
69
Load connection: If bypass switch is set to "I ON"
Load connection: If bypass switch is set to "II ON"
Rated power
7.2 kW
Rated power between L1 and L2
6.7 kW
Rated power between L1 and N
3.8 kW
Rated power between L2 and N
3.4 kW
AC current to L1 at rated power
32 A
AC current to L2 at rated power
28 A
AC power between L1 and L2 at 104°F (40°C)
6.6 kW
AC power between L1 and N at 104°F (40°C)
3.3 kW
AC power between L2 and N at 104°F (40°C)
3.3 kW
AC current to L1 at 104°F (40°C)
27.7 A
AC current to L2 at 104°F (40°C)
27.7 A
AC power between L1 and L2 at 122°F (50°C)
5.8 kW
AC power between L1 and N at 122°F (50°C)
3.0 kW
AC power between L2 and N at 122°F (50°C)
2.9 kW
AC current to L1 at 122°F (50°C)
25.3 A
AC current to L2 at 122°F (50°C)
24.3 A
Miniature circuit-breakers used in the Smartformer for
fusing
"F2" and "F3"
Rated power
11.5 kW
AC power at 104°F (40°C)
10 kW
AC power at 122°F (50°C)
9.1 kW
AC current at rated power
2 x 48 A
AC current at 104°F (40°C)
2 x 41.6 A
AC current at 122°F (50°C)
2 x 37.9 A
Miniature circuit-breakers used in the Smartformer for
fusing
"F6" and "F7"