PV plant connection

Load connection: General data

Nominal AC voltage

240 V

Rated power

9.6 kW

AC power at 104°F (40°C)

8.3 kW

AC power at 122°F (50°C)

7.6 kW

Maximum AC power for parallel grid operation to power
distribution grid

6 kW

AC current at rated power

40 A

AC current at 104°F (40°C)

34.6 A

AC current at 122°F (50°C)

31.6 A

Connection type

Spring clamp terminal / screw terminal

Maximum wire size

4 AWG

Minimum wire size at 25 A*

* Nominal current of miniature circuit-breakers "F4" and "F5"

10 AWG

Minimum wire size at 50 A*

6 AWG

Torque for screw terminal

25 in-lbs. (2.8 Nm)

Fuse type

Miniature circuit-breaker

Miniature circuit-breakers used in Smartformer

"F4" and "F5"

Nominal AC voltage

120 V / 240 V

Rated grid voltage between L1 and N

120 V

AC voltage range between L1 and N

102 V … 132 V

Rated grid voltage between L2 and N

120 V

AC voltage range between L2 and N

102 V … 132 V

Rated grid voltage between L1 and L2

240 V

AC voltage range between L1 and L2

204 V … 264 V

Nominal frequency

60 Hz

Frequency range

55 Hz … 65 Hz

Connection type

Spring clamp terminal

Maximum wire size

4 AWG

Minimum wire size

6 AWG

Fuse type

Miniature circuit-breaker