SMA SI-TB-BOX-10 User Manual
Page 68

14 Technical Data
SMA America, LLC
68
SI_TDBOX-IA-eng-IUS122211
Installation Manual
PV plant connection
Load connection: General data
Nominal AC voltage
240 V
Rated power
9.6 kW
AC power at 104°F (40°C)
8.3 kW
AC power at 122°F (50°C)
7.6 kW
Maximum AC power for parallel grid operation to power
distribution grid
6 kW
AC current at rated power
40 A
AC current at 104°F (40°C)
34.6 A
AC current at 122°F (50°C)
31.6 A
Connection type
Spring clamp terminal / screw terminal
Maximum wire size
4 AWG
Minimum wire size at 25 A*
* Nominal current of miniature circuit-breakers "F4" and "F5"
10 AWG
Minimum wire size at 50 A*
6 AWG
Torque for screw terminal
25 in-lbs. (2.8 Nm)
Fuse type
Miniature circuit-breaker
Miniature circuit-breakers used in Smartformer
"F4" and "F5"
Nominal AC voltage
120 V / 240 V
Rated grid voltage between L1 and N
120 V
AC voltage range between L1 and N
102 V … 132 V
Rated grid voltage between L2 and N
120 V
AC voltage range between L2 and N
102 V … 132 V
Rated grid voltage between L1 and L2
240 V
AC voltage range between L1 and L2
204 V … 264 V
Nominal frequency
60 Hz
Frequency range
55 Hz … 65 Hz
Connection type
Spring clamp terminal
Maximum wire size
4 AWG
Minimum wire size
6 AWG
Fuse type
Miniature circuit-breaker