6  Electrical Connection

Installation Manual

SI_TDBOX-IA-eng-IUS122211

41

6.7 Connecting the PV Plant

1. Make sure that each PV inverter is protected in the Smartformer or in the AC sub-distribution of

the PV plant according to its rated current (see the PV inverter installation manual).

2. Connect the PE conductor to a vacant spring clamp terminal of a "Grounding" connecting

terminal plate (see Section 6.5).

3. Connect the N conductor to a vacant spring clamp terminal of a "Neutral N" connecting

terminal plate (see Section 6.5).

4. Shorten insulated conductors L1 and L2 and strip the insulation by

3

8

in. (10 mm).

Danger to life due to fire in incorrectly connected PV inverter
An excessive current load can overheat the AC connection of the PV inverter and cause a cable fire.

• Protect the AC output of each PV inverter according to the maximum permissible AC electrical

current strength (see the PV inverter installation manual).

• If 1 PV inverter is connected to the Sunny Island system, protect the PV inverter with miniature

circuit-breakers "F4" and "F5" of the Smartformer.

• If several PV inverters are connected to the Sunny Island system, install the AC sub-distribution

for the PV plant according to the locally applicable standards and regulations, and protect
the PV inverters individually.

• When selecting the wire size, consult the PV inverter installation manual and adhere to the

locally applicable standards and regulations.

PV inverter

Rated current Replace the miniature

circuit-breaker?

Sunny Boy 2000HF-US / 2500HF-US / 3000HF-US 25 A

Yes: see Section 12.2

Sunny Boy 3000-US / 3800-US / 4000-US

25 A

Yes: see Section 12.2

Sunny Boy 5000-US / 6000-US

50 A

No*

* The "F4" and "F5" miniature circuit-breakers of the Smartformer are preinstalled with 50 A on delivery.

In stand-alone grids:
Sunny Boy 7000-US /8000-US

50 A

No*